Power Line Protection Zone: Widths by Voltage Class
An overhead power line’s protection zone is a strip of land on both sides of the outermost wires, whose width depends on the line’s voltage class. We give the widths from the Rules for the Arrangement of Electrical Installations (PUE), 2026 edition, Table 2.5.32; for a particular site the designer takes the final distances from the current PUE text and the line design.

Contents
- What a power line protection zone is
- Protection zone width by voltage class
- Distance to objects already located in the protection zone
- Vertical clearances: wire height above ground and buildings
- Rules for the Protection of Electrical Networks and PUE: what governs what
- How much land the line strip takes: a worked example
- A request worked through: a warehouse 18 m from a 110 kV line
- Poles near roads and streets: distances and barriers under PUE
- What to prepare before ordering poles
What a power line protection zone is
The protection zone (OZ) is a strip of land along the line’s route within which construction, planting trees and other activities that could threaten the line’s safe operation are restricted. The zone’s width is measured horizontally from the projection of the outermost wires in their undeflected position.
Protection zone width by voltage class
Per the Rules for the Arrangement of Electrical Installations (PUE), 2026 edition, Table 2.5.32:
| Line voltage, kV | Distance to the OZ boundary, m | Distance to the sanitary protection zone boundary, m |
|---|---|---|
| Over 1 to 20 | 10 | — |
| 35 | 15 | — |
| 110 | 20 | — |
| 150 | 25 | — |
| 220 | 25 | — |
| 330 | 30 | 20 |
| 500 | 30 | 30 |
| 750 | 40 | 40 |
A sanitary protection zone is additionally regulated only for lines of 330 kV and above. For lines of 500 kV and above, no objects (buildings, structures, garages) may be located in the protection zone, except industrial buildings and structures on the territory of the electrical installation itself (for them the distance from the outermost wires in their most deflected position is 10 m).
Distance to objects already located in the protection zone
If an object (building, structure, garage) is located within the protection zone, PUE (2026 edition), Table 2.5.32, separately sets the minimum distance from the outermost wires, in their most deflected position, to that object:
| Line voltage, kV | Distance to an object in the OZ, m |
|---|---|
| Over 1 to 20 | 2 |
| 35 | 4 |
| 110 | 4 |
| 150 | 5 |
| 220 | 6 |
| 330 | 8 |
| 500 and 750 | objects prohibited (except industrial buildings and structures on the electrical installation’s territory — 10 m) |
Vertical clearances: wire height above ground and buildings
In populated areas, the minimum vertical distance from power line wires to the ground and to industrial buildings under normal line operation is set by PUE (2026 edition), Table 2.5.33:
| Line voltage, kV | To ground surface, m | To industrial buildings and structures, m |
|---|---|---|
| up to 35 | 7 | 3 |
| 110 | 7 | 4 |
| 150 | 7.5 | 4 |
| 220 | 8 | 5 |
| 330 | 11 | 7.5 |
| 500 | 15.5 | 8 |
Values are determined for the greatest wire sag under the temperature and mechanical load conditions set by PUE. These are vertical clearances, not to be confused with the horizontal protection zone widths in the tables above.
Rules for the Protection of Electrical Networks and PUE: what governs what
The zone widths in the tables above match the Rules for the Protection of Electrical Networks approved by Cabinet of Ministers Resolution No. 1455 of 27.12.2022 (the 1997 Rules, No. 209, are no longer in force). The Rules also set a 2 m zone for lines up to 1 kV and 30 m for 400 kV, as well as the procedure for work in the zone, while PUE regulates the line itself: clearances and distances to objects. The same zone widths are also given in PUE (2026 edition), Table 2.5.32. Each question needs its own document:
| Question | Governed by | What to take into account |
|---|---|---|
| Is the plot inside the protection zone | Rules for the Protection of Electrical Networks | Horizontal distance from the projection of the outermost wire in its undeflected position |
| Can an object be placed in the zone | PUE and agreement with the line owner | Distance from the wire in its most deflected position |
| Is there enough height above ground and buildings | PUE (separate norms for populated areas and for non-populated and hard-to-reach areas) | Vertical distance at the greatest wire sag |
The figures are given as in PUE (2026 edition), Tables 2.5.32, 2.5.33 and 2.5.30; see also Distance Between Power Line Poles. The final distances for a site come from the design.
How much land the line strip takes: a worked example
The zone is measured from the outermost wires, not from the pole axis, so the total strip width equals twice the zone width plus the horizontal distance d (in plan) between the outermost wires. Example for a 110 kV line with an assumed d = 8 m: strip 2 × 20 + 8 = 48 m; from the line axis to the zone boundary 8 / 2 + 20 = 24 m, that is 2 × 24 = 48 m. Other voltage classes:
| Line voltage, kV | Zone on one side, m | Total strip, m |
|---|---|---|
| Over 1 to 20 | 10 | 20 + d |
| 35 | 15 | 30 + d |
| 110 | 20 | 40 + d |
| 150 and 220 | 25 | 50 + d |
| 330 and 500 | 30 | 60 + d |
| 750 | 40 | 80 + d |
The horizontal distance d (in plan) between the outermost wires depends on the pole design and voltage and is taken from the line design; the value in the example is assumed.
A request worked through: a warehouse 18 m from a 110 kV line
A warehouse wall stands 18 m from the projection of the outermost wire of a 110 kV line. The checks go in order:
- 18 m is less than 20 m: the site lies inside the protection zone;
- under PUE (2026 edition), Table 2.5.32, the distance from the wire in its most deflected position to an object in the zone is at least 4 m, so the wire may swing towards the wall by no more than 18 − 4 = 14 m; the actual swing comes from the line calculation;
- placing an object in the zone is agreed with the line owner, and the owner is notified of planned earthworks and construction ten days in advance;
- in a populated area, above the site beside the warehouse the wire must be at least 7 m above the ground under PUE (2026 edition), Table 2.5.33; outside populated areas the requirement is lower: for 110 kV, 6 m in non-populated and 5 m in hard-to-reach terrain (Table 2.5.30). The height of loads and machinery is checked against that clearance.
Poles near roads and streets: distances and barriers under PUE
Under PUE (2026 edition), cl. 2.5.173, in a populated area the distance measured horizontally from the base of a pole to the ditch or kerb of the carriageway of a street or passageway must be at least 2 m, while PUE sets no distance to pavements and footpaths. The same clause says poles on city and village streets and roads should be guarded against vehicle impact (DBN B.2.2-12, DBN V.2.3-4). On motor roads covered by cl. 2.5.214 (public roads, access roads to industrial enterprises, on-farm roads), poles standing less than 4 m from the edge of the carriageway must be protected with Group I road barriers (cl. 2.5.220).
Crossings and close approaches to such a road follow Table 2.5.46 (cl. 2.5.216). Vertically, at least 7 m is needed from the wire to the carriageway surface for lines up to 110 kV, 7.5 m for 150 kV and 8 m for 220 kV. For wires with an aluminium part of less than 185 mm² this is also checked with a wire broken in the adjacent span, where the figure is 5.5 m for lines up to 220 kV (cl. 2.5.217). Horizontally, from the base or any part of the pole to the edge of the roadbed of a road the line crosses, the distance must be not less than the pole height; in constrained conditions, to the toe of the embankment or the outer edge of the ditch, it is 5 m for lines up to 220 kV on roads of categories IA, IB and II and 2.5 m (35–220 kV) on roads of other categories. More on crossings of lines with roads, railways and pipelines is in the article Power Line Crossings with Roads, Railways and Pipelines under the PUE: Poles, Clearances, Guards.
Where the line runs parallel to a road of any category, the base or any part of a pole must stand at least the pole height plus 5 m from the edge of the roadbed, and the outermost undeflected wire of a 35–110 kV line at least 15 m from the edge of the roadbed (4 m in constrained conditions).
What to prepare before ordering poles
To select poles that fit the zone and clearances, send us:
- the voltage class, the number of circuits and the wire arrangement;
- the route plan with the objects inside the zone and their distances to the outermost wires;
- the tallest objects under the line and at crossings: roads, buildings, other lines;
- site constraints for pole locations: buildings, utilities, plot boundaries.
If the strip is limited, consider a double-circuit pole: it takes less land along the route than two separate lines. Enter the main parameters (voltage class, number of circuits, wires, clearances) in the technical specification form and attach the route plan with the objects in the zone to your request; pole types are compared in the article Power Line Poles: Multi-sided, Lattice or Reinforced Concrete.
Updated:
Reviewed by: V.V. Padalka, Chief Project Engineer
Power line protection zone: frequently asked questions
What is the protection zone width for a 110 kV line?
20 m horizontally from the outermost wires in their undeflected position, per PUE (2026 edition), Table 2.5.32.
Can you build inside a power line’s protection zone?
It is restricted — the specific distances to objects in the zone depend on the voltage class (see the table above), and for 500 and 750 kV lines objects are prohibited in the protection zone, except industrial buildings and structures on the electrical installation’s own territory.
Where do these figures come from?
From the Rules for the Arrangement of Electrical Installations (PUE), 2026 edition, Tables 2.5.32 and 2.5.33. The final distances for a particular site come from the line design.
What is the protection zone measured from: the pole or the wires?
From the ground projection of the outermost wires in their undeflected position, not from the pole. So the strip under the line is wider than twice the zone width by the horizontal distance (in plan) between the outermost wires.
What should I do before working in the protection zone?
Under the Rules for the Protection of Electrical Networks (Resolution No. 1455 of 27.12.2022, para. 25), notify the network owner ten days before planned earthworks, construction or other work begins, and obtain its written permission or a reasoned refusal. For urgent emergency repairs, para. 26 allows the work without prior approval, provided the owner is notified at the same time.
What is the protection zone for a line up to 1 kV?
The Rules set 2 m from the outermost wires, measured horizontally. The tables above cover lines over 1 kV.
Related products: Overhead power line masts · Substation gantries
More on this topic: Typical Lattice Power Line Poles: Classification and Checks · Typical Lattice Transmission Poles 35–750 kV · Steel Multi-sided Poles for 6–10 kV Lines · Power Line Pole Types by Purpose: Suspension, Tension, Angle, Terminal · Distance Between Power Line Poles: What Determines the Span Length · Steel Multi-sided Poles for 35 kV Lines