A lightning rod is earthed in one of two ways. Type A uses separate electrodes under each down-conductor; type B is a ring around the structure or a foundation loop. Below: when to use which, what sets the electrode length, which materials are used and how to deal with frost. Everything follows DSTU EN 62305-3:2021.
Lightning protection earthing is the set of electrodes in the ground that disperse lightning current from the down-conductors. Under DSTU EN 62305-3:2021 they are laid out as type A (separate electrodes under each down-conductor) or type B (a ring around the structure or a foundation loop).
Contents
Two earthing types in DSTU EN 62305-3
The standard describes two ways to lay out the earth electrodes (clause 5.4.2). In a type A arrangement each down-conductor gets its own horizontal or vertical electrodes outside the structure, and there must be at least two in total (clause 5.4.2.1). Foundation electrodes that do not close into a loop also count as type A.
Type B is an external ring conductor that touches the soil along at least 80 % of its length, or a foundation electrode closed into a loop (clause 5.4.2.2). A ring that touches the soil along less than 80 % is still classed as type A (Annex E, clause E.5.4.2.1).
For bare rock the standard recommends type B only (clause 5.4.3). It gives the same advice for structures with many electronic systems or a high fire risk.
Type A against type B
Annex E gives the earth-termination system three jobs: to carry the lightning current into the ground, to equalise potentials between down-conductors and to control potentials near conductive walls. Foundation and ring electrodes of type B do all three, while radial type A electrodes and deep vertical ones do not meet the equipotential requirement (clause E.5.4.3.1).
| What we compare | Type A | Type B |
|---|---|---|
| What it consists of | Separate electrodes under each down-conductor | A ring around the structure or a closed foundation electrode |
| Suited to | Low structures, existing buildings, rod or catenary systems, isolated systems | Roof mesh and systems with several down-conductors |
| Minimum electrodes | One per down-conductor and at least two overall | Extra electrodes, if they have to be added to the ring: at least as many as down-conductors, and not fewer than two (recommendation) |
| Length condition | Each electrode no shorter than l1 (horizontal) or 0.5 l1 (vertical) | Mean radius of the enclosed area no less than l1, otherwise add electrodes |
| Depth | Top of the electrode at least 0.5 m below ground | Ring at least 0.5 m deep and about 1 m from the walls |
Source: DSTU EN 62305-3:2021, clauses 5.4.2, 5.4.3, Annex E, clause E.5.4.2.
Electrode length and soil resistivity
The standard gives the minimum length l1 as a graph (Fig. 3; approximate values are in the table at the end of this section) of soil resistivity ρ and protection class. For classes III and IV it is 5 m at any ρ. For classes I and II it is also 5 m while ρ is low, and then it grows almost linearly.
A vertical or inclined electrode may be half as long: 0.5 l1. For a combined earth electrode the horizontal and vertical lengths are added together (clause 5.4.2.1).
The minimum lengths may be ignored if the earthing resistance of the whole system is below 10 Ω (measured at a frequency other than mains, to filter out interference). If the lengths cannot be met, type B is used. Lengthening the electrodes lowers the resistance in practice up to 60 m, and in soil above 3000 Ω·m the standard recommends type B or soil-improving compounds (clause 5.4.2.1, notes 1–3).
In a type B arrangement the mean radius r_e of the area enclosed by the ring must be no less than l1. If it is smaller, add horizontal electrodes of length l1 − r_e or vertical ones of length (l1 − r_e)/2, joined to the ring where the down-conductors arrive (clause 5.4.2.2).
| ρ, Ω·m | Class I, l1, m | Class II, l1, m | Classes III–IV, l1, m |
|---|---|---|---|
| up to 500 | 5 | 5 | 5 |
| 1000 | ≈ 20 | ≈ 9 | 5 |
| 2000 | ≈ 50 | ≈ 29 | 5 |
| 3000 | ≈ 80 | ≈ 48 | 5 |
Values read from the graph (Fig. 3, DSTU EN 62305-3:2021), accuracy about ±1 m; a design uses the graph in the standard. l1 is the length of a horizontal electrode.
Materials, concrete and corrosion
The standard gives minimum electrode sizes in Table 7; they do not depend on the protection class. The sizes for hot-dip galvanised steel are in the table at the end of this section.
Underground, an electrode corrodes. Galvanised steel can corrode in clay or damp soil, and a high chloride content makes it worse (Table 5). A galvanic link with copper can destroy it as well.
Stranded conductors of galvanised steel are not recommended in the ground: they corrode more readily, especially where they leave the soil or concrete. Galvanised steel in concrete must not run out of the concrete into the soil.
A foundation electrode goes into concrete with at least 50 mm of cover, which gives acceptable corrosion protection (clause E.5.4.3.2). Backfill the trench so that ash, coal and building rubble do not touch the electrodes. Where the soil is in doubt, corrosion is judged from experience on neighbouring sites with similar soil.
| Electrode form | Minimum size |
|---|---|
| Round rod | diameter 14 mm |
| Pipe | diameter 25 mm |
| Tape | cross-section 90 mm² |
| Solid plate | 500 × 500 mm |
Source: DSTU EN 62305-3:2021, Table 7. Galvanised steel lattice plates, copper and other forms: see the standard’s table.
Frost, drying and measurements
Burial depth and electrode type are chosen to limit freezing and drying of the soil around the electrode. The top part of a vertical electrode within the frost depth is treated as ineffective, so 0.5 m is added to the design length of each vertical electrode (clause 5.4.3; E.5.4.1).
Earth resistance changes with the seasons, so the earthing is tested after installation and then followed up. How, when and with what records is described in Lightning Protection Inspection and Maintenance. Each electrode is measured separately with the test joint opened.
The recommended overall earthing resistance is 10 Ω, but the standard stresses that correct equipotential bonding matters more than the figure (Annex E, clause E.5.4.1).
How this differs from pole earthing under the PUE
This article is about dispersing lightning current from an air terminal. Earthing of metal lighting and line poles under the PUE is a separate subject. The permitted resistance there depends on network voltage, location and soil resistivity; those rules are covered in Earthing of Metal Lighting Poles and 0.4–10 kV Overhead Lines and Earthing of Overhead Line Poles Above 1 kV under PUE:2026.
How the pole itself acts as a down-conductor, and why its joints matter more than its cross-section, is explained in Steel Mast as Air Terminal and Down-Conductor. How to choose the structure and assemble the system is in Lightning Protection for Masts and Towers.
What to send for selecting a lightning rod
The POLYGONAL company makes lightning rods and air terminals on multi-sided poles and masts 5–40 m high; ready-made options are listed in the catalogue Lightning rods 6–40 m. The lightning protection design for a building and the earthing scheme are done by the project’s designer, and installation by a licensed construction partner company.
To select a pole, send the height and site, the number of lightning rods, the protection class if already set, and soil data if you have it. Leave blank what you do not know, and we will clarify.
Updated:
Frequently asked questions about lightning protection earthing
Which type of lightning earthing should I choose?
For roof mesh and systems with several down-conductors the standard prefers type B (a ring or foundation loop). Type A suits low structures, existing buildings and rod or catenary systems. On bare rock only type B remains. The designer makes the final decision.
What resistance should a lightning rod earth have?
The standard recommends as low a resistance as possible, up to 10 Ω at low frequency, but this is a recommendation. If the system resistance is below 10 Ω, the minimum electrode lengths from the graph may be ignored (clauses 5.4.1, 5.4.2.1).
What is the minimum length of an earth electrode?
For classes III and IV it is 5 m of horizontal electrode (2.5 m vertical). For classes I and II it is also 5 m in soil up to about 500 Ω·m, and then it grows with soil resistivity. Exact values come from the graph in the standard.
Can a foundation be used as an earth electrode?
Yes. The standard recommends using interconnected reinforced concrete as a foundation electrode because it gives a very low earth resistance. It needs reliable reinforcement joints and at least 50 mm of concrete over the electrode. The specific solution depends on the design.
How does frost affect an earth electrode?
Frozen soil conducts poorly, so the top part of a vertical electrode within the frost depth is not counted. The standard recommends adding 0.5 m to the design length of each vertical electrode.
What are earth electrodes made of?
The standard permits copper, hot-dip galvanised and bare steel and other materials listed in Table 7. For hot-dip galvanised steel the minimum is a 14 mm rod, a 25 mm pipe, a 90 mm² tape or a 500 × 500 mm plate. Stranded galvanised conductors are not recommended in the ground.
Related products: Lightning protection masts and air-termination rods
More on this topic: Lightning Protection Norms: Why the Old Standard Was Withdrawn and What Applies Now · Calculating a Lightning Rod's Protection Zone: Methods and an Example · Lightning Protection of Masts and Towers: Choosing a Lightning Rod · A Steel Mast as Air-Termination and Down-Conductor per DSTU EN 62305-3 · Lightning Protection Inspection and Maintenance: Intervals, Checks, Records · Lightning Rod, Air Terminal, Lightning Protection: What's the Difference